Kelvin Generator KD100

KELVIN DIESEL GENERATORS


SPECIFICATION KELVIN GENERATOR KD100

POWER RATING PRIME POWER STANDBY POWER
Power: kVA 100 110
Power: kW 20 22 80 88
Rated Speed: Rev/Min 1500 1500
Standard Voltage: V 400 V AC. 400 V AC.
Available Voltage: V 3 Phase / 4 Wire 3 Phase / 4 Wire
Rated At Power Factor 0.8 0.8

ENGINE PRIME POWER STANDBY POWER
Rated Output 86kW 92kW
Engine Type Diesel 4 Stroke Diesel 4 Stroke
Configuration In-line 6 Cylinder In-line 6 Cylinder
Bore / Stroke 102mm / 120mm 102mm / 120mm
Displacement 5.9 Litre 5.9 Litre
Compression Ratio 16.8:1 16.8:1
Engine speed /Frequency 1500 rev/min / 50HZ 1500 rev/min / 50HZ
Aspiration Turbocharged / Aftercooled Turbocharged / Aftercooled
Cooling System Water Cooled Water Cooled
Cooling Capacity 29.7 Litre 29.7 Litre
Lubricant Capacity 14.2 Litre 14.2 Litre
Starting / Charging System 24 Volt DC 24 Volt DC
Governor Electrical Electrical
Air Filter Dry Type Dry Type

FUEL CONSUMPTION        
Engine Load 100% 75% 50% 25%
Fuel Consumption 22.0 L/h 17.0 L/h 11.0 L/h 7.0 L/h

ALTERNATOR BRAND STAMFORD
Model UC1274C
Excitation Self-Exciting, Brushless
Poles 4
Insulation Class H
Enclosure Protection IP23
Cooling Fan Cast Alloy Aluminium
Bearing Single, Double Shielded
Windings 100% Copper
Winding Pitch 2/3
Voltage Regulation A.V.R. (Electronic)
Steady State Voltage ± 1%
Under Speed Protection Standard

DIMENSIONS
Open Set Dimensions-Weight Length 2200 x Width 1030 x Height 1580 – Weight 1300 Kg
Canopy Set Dimensions-Weight Length 3300 x Width 1080 x Height 1970 – Weight 1500 Kg
 



GENERATOR SET STANDARD EQUIPMENT

ENGINE
Industrial 4 stroke water cooled diesel engine complete with air, fuel and oil filters, electric starting and charging system, engine mounted sensors for protection alarms and instruments.

COOLING
Radiator and cooling fan complete with protection guards, designed to cool engine at specified output in air temperatures up to 45°C, radiators suitable for higher temperatures are available. Low water level protection fitted as standard.

ELECTRICAL SYSTEM
24V. Axial type starter motor, battery charging alternator, high capacity lead acid battery and battery tray mounted on the generator base frame and heavy duty interconnecting cable with terminations.

EXHAUST SYSTEM
Heavy duty industrial exhaust silencer with flexible piping.

ALTERNATOR
Brushless, self exciting, self regulation, screen protected, drip proof rated in accordance with IEC60034. Voltage regulation maintained within ± 0.5% from no load to full load between 0.8 lagging and unity. All standard voltages available.

QUALITY STANDARDS
ISO9001: 2000, ISO14000, ISO3046
ISO8528 BS4999
BS5514, AS1359, ICE34
CE Compliance

We reserve the right to alter information contained within this document without prior notice.